7. Annex: NFVI Faults¶
Faults in the listed elements need to be immediately notified to the Consumer in order to perform an immediate action like live migration or switch to a hot standby entity. In addition, the Administrator of the host should trigger a maintenance action to, e.g., reboot the server or replace a defective hardware element.
Faults can be of different severity, i.e., critical, warning, or info. Critical faults require immediate action as a severe degradation of the system has happened or is expected. Warnings indicate that the system performance is going down: related actions include closer (e.g. more frequent) monitoring of that part of the system or preparation for a cold migration to a backup VM. Info messages do not require any action. We also consider a type “maintenance”, which is no real fault, but may trigger maintenance actions like a re-boot of the server or replacement of a faulty, but redundant HW.
Faults can be gathered by, e.g., enabling SNMP and installing some open source tools to catch and poll SNMP. When using for example Zabbix one can also put an agent running on the hosts to catch any other fault. In any case of failure, the Administrator should be notified. The following tables provide a list of high level faults that are considered within the scope of the Doctor project requiring immediate action by the Consumer.
7.1. Compute¶
CPU - detect: Zabbix - fault
- fail: critical
- action: switch to hot standby
RAM - detect: Zabbix - fault
- fail: critical
- action: switch to hot standby
NIC - detect: Zabbix / Ceilometer - fault
- fail: critical
- connection lost: critical
- action: switch to hot standby
PCIe - detect: SNMP - fault
- fail: Critical
- action: switch to hot standby
hard drive - detect: RAID monitoring / S.M.A.R.T / Zabbix - fault
- crash: info
- aging: info
- controller fail: critical
- action: inform OAM
Power - detect: SNMP - fault
- off: critical
- degraded: warning
- redundancy lost: warning
- threshold exceeded: warning
- action: switch to hot standby
7.2. Storage¶
controller - detect: SNMP - fault
- fail: critical
- action: switch to hot standby
temperature - detect: SNMP - fault
- too high: warning
- action: live migration
fan - detect: SNMP - fault
- fail: warning
- action: live migration
SAS link - detect: SNMP - fault
- fail: critical
- action: switch to hot standby
NIC - detect :SNMP - fault
- fail: warning
- action: live migration
7.3. Network¶
external switch interface - detect: SNMP - fault
- fail: critical
- degraded: warning
- action: live migration
SDN/OpenFlow switch - detect: ? - fault
- fail: critical
- degraded: warning
- action: live migration
Physical switch - detect: SNMP - fault
- fail: warning
- action: live migration
Physical router - detect: SNMP - fault
- fail: warning
- action: live migration
7.4. Chassis¶
fan - detect: SNMP - fault
- degraded: warning
- action: live migration
power supply - detect: SNMP - fault
- input error: critical
- redundant lost: warning
- action: live migration
7.5. Hypervisor¶
system - detect: Zabbix - fault
- restarted
- action: switch to hot standby
hypervisor - detect: Zabbix / Ceilometer - fault
- failure: critical
- action: switch to hot standby
7.6. Monitor¶
Zabbix/Ceilometer - detect: ? - fault
- unreachable: warning
- action: live migration